EARTH & SPACE / PROGRAM ATLAS

Vitality Functions

Power, fields, supervision and physical authority

NEXUS compares telemetry with the system model. The CMC provides a timing and magnetic reference. GENI uses that reference and SERAT’s power and cooling limits to coordinate field requests. AXIOM can veto a request, and local protection can trip the equipment independently.

On Earth, Living Systems Intelligence (LSI) gives operators a shared view of facility conditions and the status of essential services.

Aboard Zorak, PATRIOT helps the care team carry health observations and follow-up plans between shifts.

Try Zorak’s startup replay ↓

Zorak startup replay

Follow one Outverse coil branch from protected power to measured response. Compare a fresh CMC reference with a packet captured before the bus reset.

Read the startup procedure

Simulation

A circular blue assembly between two orange reactor assemblies, with an operator in the foreground.
Concept still from Mission Impossible at 0:31. The replay follows the Central Magnetic Core reference checks in Zorak’s current design.
Electrical power
Fusion A and B feed their own local fuses, then separate lanes through the Central Bidirectional Fuse into SERAT.
Timing and field reference
The Central Magnetic Core provides the reference that GENI uses to coordinate coil requests.

The replay starts with conditioned source power and follows a branch that is initially de-energized. Coil feedback describes the branch response. Protective effect requires its own measurement.

Explore Zorak’s full power and propulsion cycle

SERAT

Power and cooling

SERAT coordinates power distribution and cooling across ZENIT’s Earth and Space systems. It checks whether available supplies and reserves can support essential loads before it admits optional demand.

SERAT functional schematic

ZC-1 essential-electronics branch showing protected power, coolant flow, telemetry, independent protection and four operating states.

In this ZC-1 reference design, a protected bus supplies the essential electronics and coolant pump. SERAT uses power, reserve and coolant readings to advise which loads can run. Local protection can trip the branch independently.

Open full-size schematic

When the primary feed drops

The replay follows a 12 W essential circuit and an 18 W optional circuit during an 8-second interruption.

Simulated run

4 s
Primary feed drops
12 s
Primary input returns
14 s
Both circuits return to primary

Input present or circuit powered Off or unavailable

Reserve ready · simulated circuit state

The reserve supplies the essential circuit until the primary input qualifies again. The optional circuit waits for that qualification.

Essential interruption
0 s
Optional recovery after input returns
2 s
Reserve energy delivered to load
120 J
Read the simulated data
Time intervalPrimary inputReserve outputEssential loadOptional load
0–4 sPresent0 W12 W18 W
4–12 sLost12 W12 W0 W
12–14 sPresent12 W12 W0 W
14–20 sPresent0 W12 W18 W

The model uses a 36 W primary limit, up to 15 W of reserve power, and a 2-second stable-input check before returning to the primary source. It assumes adequate cooling, valid readings and instantaneous switches. A physical run will establish the actual voltage dip and switching time.

Physical bench test plan

Use an isolated low-voltage fixture with dummy loads, current limits and independent shutdown. Set the essential circuit’s minimum acceptable voltage from its equipment specification before the run. Record the fixture setup, reserve conditions and sample rate on the same run record.

  1. Establish the baseline. Confirm both loads are supplied. Record primary and reserve voltage and current, and synchronise the load measurements and controller event log.
  2. Replay the interruption. Have the test fixture remove the primary input for 8 seconds. Record voltage and current at the essential and optional loads before, during and after the interruption.
  3. Verify restoration. Record primary input return, the end of the stable-input check, and the time current actually returns to the optional circuit.
  4. Repeat the reference case. In the isolated fixture, repeat with reserve unavailable. Check that the controller reports the capacity shortfall and that local protection holds the equipment in its approved state.
MeasurementWhat to recordProposed acceptance
Essential continuityMinimum load voltage and longest interval below the selected floor.With a healthy reserve, the measured voltage stays within the essential load’s acceptance limits through transfer and restoration.
Optional recoveryElapsed time from primary input return to actual optional-load current.Current returns after the primary input qualifies. Record the full observed delay.
Reserve deliveryVoltage and current at the reserve output and essential load, with time stamps.Delivered power and energy remain within the fixture’s approved limits.

SERAT’s requested actions, local protection responses and measured load behaviour belong in the same test record. AXIOM retains the physical veto, and the ZENIT Safety Authority reviews the test evidence. IEC 61000-4-29 provides a reference for repeatable DC input interruption tests. IEC test method

Related SERAT studies

Back to frameworks ↑

GENI

Field coordination

GENI coordinates proposed field settings using sensor readings, the CMC magnetic reference and SERAT’s power and cooling limits. Space Outverse uses five layers across five hull sectors for 25 logical regions. Earth fusion uses a separate five-layer GENI Inverse concept.

Concept cutaway of a spacecraft hull section containing copper coil modules, curved supports and cooling conduits.
Concept cutaway of the coil modules and coolant lines in a vessel hull. Open full-size GENI illustration
How a field request reaches the coils
  1. InputsNEXUS observations, CMC reference, and SERAT power and cooling limits
  2. GENICalculates a request for each affected region
  3. AXIOMEnforces physical permission for the request
  4. Local coil controllersApply permitted settings within hardware limits and report measured coil state

GENI operating principles

The current GENI framework applies Equilibrium First within AXIOM’s operating limits. Compare corrective energy over the same interval and keep essential services inside their approved limits.

  • Field and protection. The plasma-to-magnetic pressure ratio describes one part of the field state. Check stability, absolute equipment limits and the measured outcome for each hazard, such as radiation dose or hull heat flux.
  • Power and motion. SERAT tracks recovered power, energy over time, heat rejection and independently supported reserves. Zorak’s propulsion model uses the vessel’s loaded mass and accounts for the momentum carried by its exhaust.
  • Frequency and return. The field fingerprint records study settings. Frequency Travel requires repeatable evidence from independently measured position and velocity.

In the FCMC-1 simulation, Centri holds the formation when Anorak exceeds its local limit, even as the fleet average improves. Readiness requires current local observations, AXIOM clearance, and SERAT power and cooling margin on each vessel.

Follow a fore-sector request

See how the offline allocator changes its request when a cooling limit or a stale reading affects the fore sector.

Simulation

GENI bench test plan

Run the three cases on an isolated controller with simulated sensors and a dummy output. Record the region requests, available capacity and output feedback on the same time base. Check that requests stay within the fixture’s limits, shortfalls are recorded and stale observations are flagged. The ZENIT Safety Authority reviews the test evidence.

CMC

Central Magnetic Core

The CMC gives Zorak’s field systems a shared magnetic and timing reference. It sits near the vessel’s centre of mass and operates alongside the separate fusion power chain.

A ring-shaped reference instrument sits on a service cradle beside equipment cabinets in a spacecraft compartment.
Concept illustration of the CMC instrument and its service bay aboard Zorak.

How it works during a voyage

  1. Share a referenceThe CMC gives field controllers a common basis for comparing the timing and magnetic conditions of their readings.
  2. Coordinate a requestGENI uses the checked reference to coordinate field requests within SERAT’s available power and cooling. AXIOM determines whether a request may proceed.
  3. Check local responseLocal controllers report what the coils actually did. NEXUS records those readings alongside the request and permission.

When Zorak’s system bus resets

  1. Hold the selected branchA CMC packet from before the reset arrives. NEXUS flags it as stale, GENI holds the new request and AXIOM withholds enable. SERAT continues to supply essential circuits in this scenario.
  2. Verify a fresh referenceA new packet agrees with the current session and an independent reference check. GENI can prepare a request within the branch’s available resources.
  3. Confirm the responseOnce AXIOM permits the request and local checks pass, the controller starts the simulated ramp. Local feedback shows how the branch responded.
Try both reference conditions in Zorak’s startup replay ↑
What the simulation can verify

The replay illustrates the logic for one initially de-energized branch. Reference quality, permission and measured response are separate records. The protective effect of a field would require a separate physical test.

AXIOM

Physical authority

AXIOM retains the final physical veto over requested operations. A local interlock can trip its own equipment independently. NEXUS supervises and records events, while the ZENIT Safety Authority authorizes tests and reviews their evidence.

Concept cutaway of a safety cabinet with electronics and a physically separate compartment for hardwired protection.
Concept cutaway of a divided safety cabinet. The teal bay illustrates command permission, and the relay bay illustrates independent protection. Open full-size AXIOM illustration
Two paths to the controlled equipment

Command path

  1. Operation requestGENI, SERAT or another controller requests a permitted operation
  2. AXIOM permissionPermit the request or veto it before actuation

Independent trip path

  1. Local fault detectionHardwired protection can trip the affected branch even during a permitted run

Controlled output. The branch enables when permission and local checks agree. An independent trip takes it to its approved protective state. Output feedback records the result.

Replay a permission decision

Follow the enable request, the local interlock and the measured state of a simulated dummy load.

Simulation

A valid request passes the AXIOM gate. With the local interlock healthy, simulated feedback confirms that the dummy load energizes.

AXIOM gate
Permit
Local interlock
Healthy
Output feedback
Energized

The replay follows a single isolated test branch. On a vessel, the approved protective action depends on the operating phase and the essential services that need to remain available.

AXIOM bench test plan

Use an approved low-voltage fixture with a dummy load and observe both the request and switched output. Apply a veto before enable and a local trip after enable. Repeat the local-trip case with the supervisory link disconnected. Record the order of events, the measured output and whether the branch stays tripped until reset.

NEXUS

Supervisory digital twin

NEXUS compares verified telemetry with the expected behaviour of ZENIT equipment. It flags trends and gaps in the evidence, advises operators and records decisions. AXIOM retains physical veto authority, and local interlocks can trip equipment independently.

Open telemetry station with a sensor-input rack, a two-screen console and a protected recorder bay.
Concept illustration of a NEXUS telemetry station with separate data intake, operator displays and local recording. Open full-size NEXUS illustration
How a reading becomes an assessment
  1. Local instrumentsSample equipment and attach source, measurement time and sequence
  2. Telemetry verificationCheck source, age, sequence and integrity before forwarding readings
  3. NEXUSCompare accepted readings with the model and flag disagreements
  4. Crew display and recorderShow the assessment and its data quality. Preserve the original event times onboard.

Follow a cooling-flow report

Compare what the vessel and fleet can see when a report expires or the reporting link drops.

Inspect the shared quantity and event checks: energy closure, unique credits, evidence maturity, force density and separate crossing/receipt records.

Simulation

A fresh, verified coolant-flow reading reaches onboard NEXUS. It compares the sample with the expected range and records the original measurement time.

Onboard assessment
Current
Fleet view
Current
Local interlock
Available

The example assumes powered onboard instruments, a separate local protection path and a fleet report that includes this channel. After reconnection, new reports qualify on their own evidence and delayed events retain their original measurement times.

NEXUS bench test plan

Use a simulated instrument and record its readings on the onboard and fleet displays. Send an expired sample, disconnect the fleet report path and restore it with a fresh sample. Check that the displays distinguish current, stale and disconnected states, and that local protection remains available throughout. Compare the event log with the instrument’s time stamps.

AGCM

Navigation and docking

AGCM checks route geometry and the history of the vessel’s position reports before a close approach. During space docking, it compares where the shuttle and host report being, how their docking interfaces line up, and how reliable those observations are.

A wingless shuttle lines up with a host vessel’s docking collar while the two craft are still apart.
A Qi shuttle approaches a compatible host in space. The gap illustrates the approach phase before capture.

From position reports to an approach assessment

  1. Compare observationsUse their timestamps, reported uncertainty and a common coordinate frame.
  2. Assess alignmentAGCM checks the approach path and whether the interfaces line up. NEXUS presents the assessment and flags gaps in the evidence.
  3. Check permission and capture separatelyAXIOM and local protection retain authority over movement. The receiving crew confirms measured capture and support before handover.

Can the shuttle continue its approach?

Compare three sets of navigation reports for the same shuttle and host.

Simulation

Independent observations agree within the study’s limits. Alignment supports an approach request, which still needs separate permission and local checks.

Observations
Current and consistent
AGCM assessment
Alignment verified
Approach decision
Request may proceed to checks

This conceptual exercise covers approach evidence. Capture, load transfer and clearance for crew transfer each require their own confirmation.

PATRIOT

Crew health and medical handover

A crew member’s health history should be available to the medic taking over their care. PATRIOT is ZENIT’s proposed onboard record for observations, readings and follow-up in Zorak Sick Bay.

A medic with a tablet listens to a seated crew member in a spacecraft medical alcove.
A routine check in Zorak Sick Bay. Concept illustration.

How a reading follows a crew member

  1. Take a readingA medic measures temperature and asks how the crew member feels.
  2. Record the contextPATRIOT keeps the observation, its source and the time it was taken.
  3. Review at handoverThe next medic can compare earlier readings and see what needs follow-up.

The medical team interprets the information and decides what care is needed.

What changes for people aboard

Routine check

A flagged reading prompts a medic to review the entry and decide whether to repeat it or follow up. Crew members can report symptoms any time, even if the record shows no alert.

Shuttle handover

The receiving medic verifies the patient and confirms receipt of the observations and pending follow-up. Delayed or incomplete entries stay marked so the next team can judge what needs checking.

Network outage

The local team keeps a manual time-stamped record and reconciles it when service returns. The crew can still reach a medic, and cabin alarms operate through their own systems.

Who sees what

Crew member
Access to their own record and follow-up plan.
Care team
Individual readings and relevant history for treatment, isolation and return-to-duty decisions.
Ship operations
Information needed to act, such as a duty restriction or a request to check ventilation.

The proposed access rules keep personal readings within the care team. Cabin life support maintains habitable conditions while medics look after the people aboard.

Design limits and references

PATRIOT is a concept. Clinical performance, alert workload, access controls and the offline handover need verification. These references describe the spaceflight context for health records and medical support.

Living Systems Intelligence (LSI)

LSI is ZENIT Earth’s proposed operational model for facilities and infrastructure. It brings equipment readings, environmental conditions and maintenance records together so operators can see which services are available, what has changed and what still needs to be checked.

Operator at a bank of monitoring screens overlooking a snow-covered coastal research facility.
Concept illustration of the Earth Research Facility’s operations room. The LSI view brings water, ventilation and reserve power together at the operator’s desk.

How LSI builds the facility view

  1. Collect local readingsInstruments report water level, air quality and reserve power with their source and measurement time.
  2. Check the evidenceThe telemetry gateway checks readings before NEXUS compares them with expected conditions and flags discrepancies.
  3. Show condition and confidenceLSI shows which services are available and marks missing, stale or conflicting evidence as unassessed. The local record preserves events and operator notes for follow-up.

During a SafeSpot winter outage

The grid and regional data link go down at the Critical Continuity SafeSpot. In this scenario, the SERAT reserve keeps the local monitors and recorder powered. Operators can still see current readings from connected on-site instruments. The regional display marks the site disconnected and shows when it last received a report.

If the water-level reading expires, LSI marks water availability as unassessed and displays the time of the last sample. The operator checks the local indicator and confirms a fresh reading before sharing the status again. AXIOM retains physical veto authority, and local interlocks can still trip equipment independently.

Technician checking an instrument beside pipes and valves in a SafeSpot utility room.
Concept illustration of a local instrument check in a SafeSpot utility room.

LSI and NEXUS at a glance

LSI
Presents Earth facility conditions, service availability and the quality of the evidence in a form operators can use.
NEXUS
Analyses telemetry, assesses likely changes and coordinates permitted responses. Its assessments inform the LSI view at the Earth Research Facility.

The article describes a ZENIT Earth concept. The outage and illustrations show how it could work.